Conduit Fill Calculator
Check how many wires fit in EMT, PVC, rigid or flexible conduit by trade size, with the NEC 40% fill rule, and the box fill count for a device box. Add each group of wires with its insulation and size to get the percent fill, pass or fail at the NEC Chapter 9 limits, the smallest trade size that passes and the most of one wire that fits. Based on the 2023 NEC. Local amendments and the authority having jurisdiction (AHJ) govern.
Your numbers
Allows 60% fill (Chapter 9, Note 4).
Wires in the conduit
Up to 6 rows, one per wire size and insulation. Count the ground wire too.
Conduit fill
–
- NEC Chapter 9, Table 1
- –
- Wire area
- –
- Conductors
- –
- Conduit area (100%)
- 0.533 in², 3/4 in EMT
- Smallest EMT that passes
- –
- Most of one wire alone
- –
Based on the 2023 NEC. Local amendments and the authority having jurisdiction (AHJ) govern.
Include the equipment grounding conductor in the wire rows (Chapter 9, Note 3). For a single wire size, NEC Annex C lists the same counts.
The calculation runs in your browser and ParrotNotes does not store your numbers. They sit in the page address so you can bookmark or share the result.
How the conduit fill is calculated
Each wire's area comes from NEC Chapter 9: Table 5 for insulated conductors (THHN/THWN-2, XHHW-2, THW) and Table 8 for bare stranded conductors. The calculator multiplies each area by the count, adds the rows, and divides by the internal area of the conduit from Table 4, which is listed separately for EMT, rigid metal conduit, IMC, PVC Schedule 40 and 80, flexible metal conduit and liquidtight flexible metal conduit. Equipment grounding conductors count toward the fill (Chapter 9, Note 3).
Worked example: three 6 AWG THHN and a 10 AWG THHN ground. 3 × 0.0507 + 0.0211 = 0.1732 in². That is four conductors, so the limit is 40%. 3/4 in EMT has 0.533 in², so the fill is 32.5% and it passes. 1/2 in EMT (0.304 in²) would be 57%. In PVC Schedule 80, whose thicker wall leaves less room, 3/4 in (0.409 in²) is 42.3% and fails, so the smallest Schedule 80 that passes is 1 in.
The maximum-count line works the way NEC Annex C does: 40% of the conduit area divided by one wire's area, rounded down, except that a decimal of 0.8 or more rounds up (Note 7). For a single wire size the Annex C tables give the same answers without any arithmetic; the calculator is for mixed sizes and for checking a table you have on site.
Why 53%, 31% and 40%
The limits in Chapter 9, Table 1 leave room to pull the wires without damaging the insulation and to let heat escape. One conductor may take 53% of the area, two conductors 31% (two round wires in a round pipe can wedge across the diameter), and three or more 40%. A nipple 24 inches long or less between enclosures may be filled to 60% (Note 4), and the ampacity adjustment for more than three current-carrying conductors does not apply to it (310.15(C)(1)).
Fill is a maximum, not a target. Long pulls, several bends and large conductors pull more easily well below 40%. And the more current-carrying conductors share a conduit, the more their ampacity must be reduced under 310.15(C)(1): the wire size may change before the conduit does.
Box fill under NEC 314.16
Box fill counts conductor volumes, each worth the cubic inches in Table 314.16(B) for its size: 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00 and 6 AWG 5.00. Every conductor that enters the box and is spliced or terminated counts one, and so does one that passes straight through; an unbroken loop at least twice the free length in 300.14 (12 inches) counts two. Pigtails that start and end inside the box do not count.
Then add: one volume for internal cable clamps (whatever their number), one for each type of support fitting such as a fixture stud or hickey, both at the largest conductor in the box; two for each device yoke, at the largest conductor connected to that device; and one for up to four equipment grounding conductors, plus a quarter volume for each one over four, at the largest ground. Compare the total with the box volume from Table 314.16(A), or the volume marked inside a nonmetallic box, plus the volume marked on a plaster ring, extension ring or raised cover.
What the calculator does not cover
Compact conductors (Chapter 9, Table 5A), multiconductor cables pulled into a conduit (counted as one conductor of their outside diameter, Note 9), 3/8 in flexible conduit (its own tables in 348.22 and 350.22) and other raceways such as ENT, LFNC and HDPE are not included. Use the manufacturer's diameter for any wire whose insulation differs from the Table 5 types.
The result checks fill only. Ampacity adjustment for bundled conductors, the conductor's temperature rating and the total degrees of bends between pull points (360° under 358.26 and the matching sections) are separate rules. The calculator follows the 2023 NEC; local amendments and the authority having jurisdiction decide what passes inspection.
For electricians and estimators on a walk-through
On a walk-through the circuit list grows in conversation: two more 20 A circuits for the shop, a 10 AWG ground, a separate run for the charger, PVC underground and EMT inside. Each change can move a run up a trade size, and the fittings, straps and labor follow.
Run each homerun here while the customer is still talking, so the takeoff and the quote use the conduit sizes the job actually needs.
Based on the 2023 NEC. Local amendments and the authority having jurisdiction (AHJ) govern. Check the insulation printed on the wire and the volume marked on the box before relying on the result.
Sources, read on 2026-10-24:
- NFPA 70, National Electrical Code (2023): Chapter 9 Tables 1, 4, 5 and 8, Notes 3, 4, 7 and 9, Annex C, 314.16 and Tables 314.16(A) and (B)
- PDHonline course E276, Conduit Fill Tables: Chapter 9 Table 4 dimensions for EMT, IMC, RMC and PVC Schedule 40 and 80
- International Code Council sample pages: Chapter 9 Table 5, dimensions and areas of insulated conductors
- Open Exam Prep, Outlet and Junction Box Sizing: Table 314.16(A) metal box volumes
- EC&M, Box Fill Calculations: how clamps, fittings, yokes and grounds are counted
Choosing the wire first? The wire size calculator checks ampacity and voltage drop together, and the voltage drop calculator checks a long run.
More for electrical trades: Electrical distributor sales, What is a submittal, Construction daily report, Solar sales.
The circuit list changes on the walk-through. Keep it.
Homeruns, grounds and conduit runs get decided out loud: two more 20 A circuits, PVC underground, a 10 AWG ground for the charger. Record the walk-through in ParrotNotes and get a structured note, a summary and the action items, so the takeoff matches what the customer asked for. Free for 100 minutes of recording a month.
Get Started FreeRelated tools
- Wire Size CalculatorFind the AWG wire size for a load by ampacity and voltage drop, from amps, run length, voltage and phase, for copper or aluminum.Open the tool
- Voltage Drop CalculatorFind the voltage drop and percent drop on a copper or aluminum wire run by AWG size, length, load and phase, against the 3% and 5% guides.Open the tool
- Ohm's Law CalculatorEnter any two of volts, amps, ohms and watts to get the other two with the formula used, plus amps to watts and kVA to amps for single and three phase.Open the tool
- Generator Wattage CalculatorAdd up the running and starting watts of the appliances you want to power to size a portable or home standby generator, with a margin.Open the tool