Wire Size Calculator
Find the AWG wire size for a load by ampacity and voltage drop, from amps, run length, voltage and phase, for copper or aluminum. Enter the load, the voltage and the one-way run to get the minimum size for the current, the minimum for your allowed drop, and the size to use, with its voltage drop. An estimate: a licensed electrician and the local code decide.
Your numbers
120, 208, 240, 277, 480; 12, 24 or 48 for DC.
Source to load, along the route.
3% is the NEC's recommendation for a branch circuit, 5% for feeder and branch together.
Runs at full current for 3 hours or more; sized at 125%.
Recommended wire size
–
- Set by
- –
- Minimum by ampacity
- –
- Minimum for 3% drop
- –
- Voltage drop at the recommended size
- –
- Voltage at the load
- –
- Current the wire is sized for
- –
- Ampacity of the recommended size
- –
- Smallest standard breaker for the load
- –
Ampacity from NEC Table 310.16 at 30°C ambient with no more than three current-carrying conductors together. Hotter spaces, more conductors in one raceway and the terminals' temperature rating can call for a larger wire.
An estimate: a licensed electrician and the local code decide.
The calculation runs in your browser and ParrotNotes does not store your numbers. They sit in the page address so you can bookmark or share the result.
How the wire size is worked out
Two checks, and the larger answer wins. First, ampacity: the smallest wire whose rating in NEC Table 310.16, in the temperature column you choose, covers the current. A continuous load is counted at 125%, and 14, 12 and 10 AWG copper are held to their 240.4(D) breaker limits of 15, 20 and 30 A. Second, voltage drop: the smallest wire whose drop over the one-way length stays at or under the percent you allow, using the NEC Chapter 9 Table 8 resistance at 75°C.
Worked example: a 40 A, 240 V single-phase load 150 feet away, copper, 75°C column, 3% allowed. By ampacity, 10 AWG is capped at 30 A, so 8 AWG (50 A) is the minimum. By voltage drop, 3% of 240 V is 7.2 V; 8 AWG drops 2 × 40 × 0.778 × 150 ÷ 1,000 = 9.34 V, too much, and 6 AWG drops 5.89 V, or 2.46%. The recommended size is 6 AWG copper, set by voltage drop. The smallest standard breaker for the load is 40 A.
Which temperature column to use
The default is the 75°C column, which applies when the wire and everything it lands on (breaker, panel, disconnect, equipment) are rated at least 75°C. NEC 110.14(C) says circuits of 100 A or less, or wire from 14 to 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C. If you are not sure what the terminals are marked, choose 60°C.
The 90°C column is for conductors like THHN, THWN-2 and XHHW-2 and is where adjustment starts when a wire runs through a hot attic or shares a raceway with more than three current-carrying conductors. After derating, the result still cannot exceed the terminal rating. Those corrections are not in this calculator.
Breaker and fuse sizing
The calculator shows the smallest standard breaker or fuse rating, from NEC 240.6(A), at or above the design current. The wire's ampacity has to be at least that rating, except that 240.4(B) lets you use the next standard size up when the wire's ampacity falls between standard sizes, on circuits up to 800 A that do not feed several receptacles for cord-and-plug equipment. The 240.4(D) limits on 14, 12 and 10 AWG copper always apply.
Dwelling services and the main feeder of a house follow 310.12, which allows a smaller size than Table 310.16. Motors (Article 430), air conditioners and heat pumps (Article 440, using the nameplate's minimum circuit ampacity and maximum breaker), EV chargers and solar circuits each add their own multipliers. Use the nameplate and the article for those.
AWG ampacity and resistance chart
The values the calculator uses. Ampacity in amps from NEC Table 310.16 (not more than three current-carrying conductors, 30°C ambient); DC resistance in ohms per 1,000 feet at 75°C from NEC Chapter 9, Table 8 (stranded). A dash means the table lists no value. Breakers on 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum are limited by 240.4(D).
| Size | copper, amps | aluminum, amps | Ω per 1,000 ft | |||||
|---|---|---|---|---|---|---|---|---|
| 60°C | 75°C | 90°C | 60°C | 75°C | 90°C | Cu | Al | |
| 18 AWG | – | – | 14 | – | – | – | 7.95 | 13.1 |
| 16 AWG | – | – | 18 | – | – | – | 4.99 | 8.21 |
| 14 AWG | 15 | 20 | 25 | – | – | – | 3.14 | 5.17 |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | 1.98 | 3.25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | 1.24 | 2.04 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | 0.778 | 1.28 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | 0.491 | 0.808 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | 0.308 | 0.508 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | 0.245 | 0.403 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | 0.194 | 0.319 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | 0.154 | 0.253 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | 0.122 | 0.201 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | 0.0967 | 0.159 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | 0.0766 | 0.126 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | 0.0608 | 0.1 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | 0.0515 | 0.0847 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 | 0.0429 | 0.0707 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | 0.0367 | 0.0605 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | 0.0321 | 0.0529 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | 0.0258 | 0.0424 |
For electricians and solar installers on a job walk
The inputs that decide the size come up as you walk the job: the load, where the panel is, how the run gets there, whether it goes through the attic. On a long run the wire is often the largest material cost on the quote, so a size up or down changes the price.
Run the circuit here while you are still on site, then write the size and the reason into the quote, so the customer sees why the run to the shop needs bigger wire than the one to the kitchen.
An estimate: a licensed electrician and the local code decide. Ambient temperature, conductors bundled in one raceway, terminal ratings and the equipment's nameplate all affect the final size.
Sources, read on 2026-10-23:
- NFPA 70, National Electrical Code (2023): Chapter 9 Table 8 conductor resistance, Table 310.16 ampacity, Informational Notes to 210.19 and 215.2
- Table 310.16 ampacities as reproduced by LugsDirect (2020 edition), checked against the 2023 values on 2026-10-23
Already picked the wire? The voltage drop calculator checks one size, with parallel sets. Sizing the load first? Try the BTU calculator for heating and cooling, or the solar calculator for an array.
More for electrical and solar trades: Solar sales, Electrical distributor sales, Construction daily report, HVAC sales.
The load and the run get said on the walk-through.
Electricians and solar installers hear the numbers out loud on site: a 50 A range circuit, 150 feet to the shop, a subpanel in the garage. Record the walk-through in ParrotNotes and get a structured note, a summary and the action items, so the quote has every run and load in it. Free for 100 minutes of recording a month.
Get Started FreeRelated tools
- Voltage Drop CalculatorFind the voltage drop and percent drop on a copper or aluminum wire run by AWG size, length, load and phase, against the 3% and 5% guides.Open the tool
- Ohm's Law CalculatorEnter any two of volts, amps, ohms and watts to get the other two with the formula used, plus amps to watts and kVA to amps for single and three phase.Open the tool
- Solar Panel CalculatorSize a solar system from your electricity use and sun hours: system size, number of panels, rough cost, yearly savings and payback years.Open the tool
- BTU and AC Size CalculatorEstimate the BTUs and air conditioner tonnage a room or home needs from its size, sun, shade and occupants, as a rule of thumb before a load calculation.Open the tool