Heat Loss Calculator

Estimate a room's or home's heat loss in BTU per hour from walls, windows, ceiling, floor and air leakage, to size heating before a full load calculation. Each surface gets U × A × ΔT, the air gets 0.018 × volume × air changes × ΔT, and the table shows where the heat goes.

Your numbers

For one room, enter only the surfaces that face outdoors or an unheated space.

°F

The temperature the heating must hold. 70 °F is filled in; change it.

°F

Your location's winter design value from ACCA Manual J or ASHRAE climate data.

sq ft

Sets the air volume, and the ceiling and floor areas if those are left empty.

ft
sq ft

R-13 filled in (a 2×4 wall with batts); the whole wall is lower because of the studs.

sq ft

From the NFRC label. 0.50 filled in: double glazed (0.43 to 0.57); single glazed is 0.91 to 1.11.

sq ft

0.17 filled in: the ENERGY STAR limit for an opaque door. Older doors lose more.

sq ft

Empty uses the heated floor area. Type 0 for a room with heated space above.

sq ft

Empty uses the heated floor area. Type 0 for a floor over heated space or on a slab.

°F

A crawl space or basement in winter. Empty uses the outdoor design temperature, the cautious case.

0.5 filled in: new, careful construction. About 1.0 for an older, leaky house; 0.33 for a very tight one.

House heat loss at design conditions

–

Design temperature difference
–
Through walls, windows, doors, ceiling and floor
–
Air leakage
–
Heat loss per °F of difference (UA)
–

The calculation runs in your browser and ParrotNotes does not store your numbers. They sit in the page address so you can bookmark or share the result.

How the heat loss calculation works

Heat leaves a heated space two ways: through the surfaces (conduction) and with the air that leaks out and is replaced by cold air (infiltration). For each surface, the loss is Q = U × A × ΔT: the U-factor, the area in square feet and the difference between the indoor and outdoor design temperatures. For the air, it is 0.018 × volume × air changes per hour × ΔT. Add them all for the design heat loss in BTU per hour: the heat the system has to replace on a design-cold day.

Worked example: a 1,500 sq ft single-story house with 8 ft ceilings, 70 °F indoors and 5 °F outdoors, so ΔT = 65 °F. Walls 1,200 sq ft at R-13: 1,200 ÷ 13 × 65 = 6,000 BTU/h. Windows 200 sq ft at U 0.50: 200 × 0.50 × 65 = 6,500. Doors 40 sq ft at U 0.17: 442. Ceiling 1,500 sq ft at R-30: 3,250. Floor 1,500 sq ft at R-19 over a vented crawl space: 5,132. Air: 12,000 cubic feet × 0.5 × 0.018 × 65 = 7,020. Total: about 28,344 BTU per hour.

Enter wall area net of the windows and doors, which have their own lines. For one room, enter only the surfaces that face outdoors or an unheated space, and the room's own floor area and ceiling height for the air.

R-value and U-factor

Insulation is rated by R-value, its resistance to heat flow; the higher, the better. Windows and doors are rated by U-factor, the heat that gets through per square foot, per hour, per degree; the lower, the better. They are inverses: U = 1 ÷ R. Penn State's window label guide puts it this way: an R-value of 4.0 is the same as a U-factor of 0.25.

The R-value on an insulation bag is for the insulation, not the whole wall: studs, plates and headers carry heat around it, so a framed wall's whole-assembly R is lower than the batt's. If you know the assembly value, use it; the calculator takes what you type.

U-factors and R-values to start from

Starting points for the inputs, from the sources below. Use the label, the spec sheet or what you find on site whenever you can.

Window and door U-factors and recommended insulation R-values, with their sources
SurfaceValueSource
Window, single glazedU 0.91 to 1.11Penn State EGEE 102
Window, double glazedU 0.43 to 0.57Penn State EGEE 102
Window, triple glazedU 0.15 to 0.33Penn State EGEE 102
Window, ENERGY STAR v7.0 Northern zoneU 0.22 or lessENERGY STAR v7.0 spec
Window, ENERGY STAR v7.0 Southern zoneU 0.32 or lessENERGY STAR v7.0 spec
Door, opaque, ENERGY STAR v7.0U 0.17 or lessENERGY STAR v7.0 spec
Door, half glass or less, ENERGY STAR v7.0U 0.23 or lessENERGY STAR v7.0 spec
Attic, recommended when adding to an empty oneR30 (zone 1) to R60 (zones 4 to 8)ENERGY STAR
Floor over unheated space, recommendedR13 (zones 1 and 2) to R38 (zones 7 and 8)ENERGY STAR
Basement or crawl space wall, battR13 or R19 by zoneENERGY STAR

Air changes per hour

Air changes per hour (ACH) is how many times the air in the heated volume is replaced by outside air in an hour under normal conditions. The Los Alamos solar heating handbook puts the usual range at one-half to one air change per hour. Build It Solar's calculator suggests 0.33 for a very tight house, 0.5 for new, careful construction and 1.0 for typical existing construction, with a question mark on the last.

A blower door test measures leakage at 50 pascals (ACH50), which is not the same number: it is many times the natural rate. Do not type an ACH50 figure here. If you only have ACH50, ask the energy auditor for the natural air change rate.

Design temperatures

The result is only as good as ΔT. The indoor design temperature is the one the system has to hold; the outdoor design temperature is a cold value for the location that is exceeded only a small share of winter hours, taken from ACCA Manual J or the ASHRAE climate data, not the coldest day on record. The NGMA heat loss standard notes that the 97.5% winter dry bulb from the ASHRAE data is common practice.

Floors over a crawl space or basement lose heat to that space, not to the outdoors. If you know its winter temperature, type it under "Temperature under the floor"; left empty, the calculator uses the outdoor design temperature, which overstates the floor loss for most basements. Slab-on-grade floors lose heat mainly at the edges and are not modelled here.

Before you size equipment

This is the heat-loss half of a load calculation, done with your numbers. ANSI/ACCA Manual J is the standard method for residential loads: it works room by room with tables for each assembly, counts duct losses and sets the design conditions, and Manual S then selects the equipment. This page is not a substitute for that calculation. Use it to understand where the heat goes, to check a quote, and to see what an upgrade such as new windows or attic insulation would change.

For HVAC and home-services reps

The table under the result is a sales conversation: it shows the homeowner which part of the house loses the most heat. Change one line, say the windows from U 1.0 to U 0.30 or the attic from R-19 to R-49, and the drop in BTU per hour shows what the upgrade is worth before anyone talks price. Measure, note what you see in each room, and run the full load calculation before you quote equipment.

Sources, each read on 2026-10-28. All results are estimates:

Picking the furnace? The furnace size calculator turns a load into an input rating at your AFUE. For cooling, the BTU and AC size calculator gives the rule-of-thumb size, and the insulation calculator works out the bags or batts for a new R-value.

More for HVAC and home-services reps: HVAC sales, HVAC sales training, Home improvement sales.

The drafty rooms come up on the walk-through

So do the single-pane windows in the back bedroom, the attic nobody has looked at and last winter's bills. Record the visit in ParrotNotes and get a structured note, a summary and the action items, so the areas, R-values and complaints are in the note when you work out the load. Free for 100 minutes of recording a month.

Get Started Free

Related tools

Heat loss FAQ